・ DALI Dimming Brightness ・ Can Be Control With Groups ・ Input Voltage Range(100-240Vac) ・ Power Factor Corrected (>0.9) ・ Low Standby Power (<0.3W) ・ High reliability to assure LED long life ・ Protections Short Circuit / Over Load / Over Voltage/Over Temperature ・ EN61347,CISPR 15,EN55015
Technical Data
Nominal Input Voltage:
100 – 240 VAC
Line Current, nominal:
0.2A MAX.
Mains Frequency:
50/60 Hz
Rated Power factor:
≥ 0,9 (full load) @ 230V
Power Loss in no load condition
<0.3W
Protection Class:
II
Output Current:
600-900 mADC
(Remark)
8–40VDC 600-1000mA
Output voltage:
8–40VDC
(Remark)
Maximum < 50 VDC
Output Power:
Maximum 40W
No-load proof:
Yes
Short circuit protection:
Automatic, reversible
Overload protection:
Automatic, reversible
Over temperature protection:
Automatic, reversible
Ambient temperature range, ta:
-20 °C to +45 °C
Max. case temperature at tc point:
75 °C
Dimming Range
Normal 1%.....100% full load condition at 230V
ECG Lifetime:
30,000h or 3 years Fail rate <10%
(Remark)
at use of Under normal conditions
Cable cross section input side & output side
0.5-2.5mm
(Remark)
Solid and flexible
Wire preparation length Input side & output side
7-8 mm
Geometry (l x b x h):
134 x 56 x 30mm
Weight:
140 g
Safety Standard:
IEC 61347-1, IEC 61347-2-13, IEC 62384
Radio interference:
CISPR 15
Harmonic content:
IEC 61000-3-2
Immunity:
IEC 61000-3-3,IEC 61547
Surge capability:
L-N: 500V
Galvanic isolation
3,75 kVrms
primary/secondary :
SELV-equivalent
MODEL List
Model
Input Voltage (V)
Output current (mA)
Output Voltage (V)
PF
Efficiency
Flicker
ALD24-40060DAA2
100-240
600
20-40
>0.9
87%
Flicker-Free
ALD30-43070DAA2
100-240
700
20-43
>0.9
87%
Flicker-Free
ALD30-40075DAA2
100-240
750
20-40
>0.9
87%
Flicker-Free
ALD30-40080DAA2
100-240
800
20-40
>0.9
87%
Flicker-Free
ALD40-40090DAA2
100-240
900
20-40
>0.9
87%
Flicker-Free
Submit Questions Online
Welcome to ALLOOKING,Thanks a lot!